Modbus/RTU-CAN converter
- Brand:
- GUANGCHENG TECHNOLOGY CO.,LTD.
- Model:
- GCAN-204
- Application:
The serial communication device is connected to CAN-bus;
PLC connection CAN-bus;
Modbus RTU and CAN communication;
CAN-bus and serial bus gateway;
Monitor industrial site network data;
Beginners learn CAN;
CAN industrial automation control system;
Collect low-speed CAN network data.
-
1 Overview
GCAN-204 converter has one CAN-Bus interface, one serial interface. The GCAN-204 integrates the Modbus RTU protocol. With the GCAN-204 , user can use the serial bus connect to other equipment (with Modbus RTU protocol) access the CAN-Bus communication interface.
GCAN-204 has integrated isolation protection module. Using DIN railway fixed, it can be easier to integrate into the control cabinet.2 Properties at a glance
Modbus slave support function code: 03H, 04H, 06H, 16H
Serial baud rate: 600bps ~ 115200bps
CAN-Bus supports CAN2.0A and CAN2.0B frame format, conform to ISO/DIS 11898 standards
CAN baud rates: 5Kbps ~ 1Mbps
CAN-Bus isolation module insulation voltage: DC 1500V
Power supply: 9~30V (20mA,24V DC)
Interface using terminal blocks
Installation method: DIN rail
Working temperature range from -40 to 85 °C
Size: (L)113mm * (W)100mm * (H)21mm3. Examples
The user can use the included serial debugging assistant to send Modbus instruction debugging.
Please note: choose "hexadecimal display" and "hexadecimal send" when using the serial debugging assistant.3.1 Receive CAN data
For example, configure the Modbus slave address: 1, Modbus register first address: 0x01, CAN: standard frame, frame ID: 0x181, CAN frame data: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x07, 0x08.
User Modbus master sends request frame:
01 03 00 01 00 04 15 C9
GCAN-204 response frame:
01 03 08 02 01 04 03 06 05 08 07 17 C1
Please note that the CRC is calculated by the CRC16 checksum calculator. (With disk)
At this point, the GCAN-204 module has received a data frame with a frame ID of 0x181 from the CAN terminal of other equipment.3.2 Transmit CAN data
For example, Modbus slave address: 1, Modbus register first address: 0x101 (decimal: 257), function code: 16 (10H), CAN: standard frame, frame ID: 0x201, CAN frame data: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x07, 0x08.
User Modbus master sends request frame:
01 10 01 01 00 04 08 02 01 04 03 06 05 08 07 CB 2E
GCAN-204 response frame:
01 10 01 01 00 04 91 F6
Please note that the CRC is calculated by the CRC16 checksum calculator.
At this point, the CAN terminal of other equipment has received a data frame with a frame ID of 0x201 from the Modbus side of the GCAN-204 module.4. Technical Specifications
- Modbus slave support function code: 03H, 04H, 06H, 16H
Serial baud rate: 600bps ~ 115200bps
CAN-Bus supports CAN2.0A and CAN2.0B frame format, conform to ISO/DIS 11898 standards
CAN baud rates: 5Kbps ~ 1Mbps
CAN-Bus isolation module insulation voltage: DC 1500V
Power supply: 9~30V (20mA,24V DC)
Interface using terminal blocks
Installation method: DIN rail
Working temperature range from -40 to 85 °C
Size: (L)113mm * (W)100mm * (H)21mm
If you have technical problems, please contact us by email. We will reply to you within 24 hours after receiving the mail.
After sales technical mailbox: 2881884588@qq.com-
GCAN-204 (CAN to Modbus RTU) converter
User Manual(Click to view)Please ask for more information to the Engineer.
E-mail:2881884588@qq.com